INPUT DATA
Number of MPP trackers | 2 |
Max. input current (Idc max) | 12 / 12 A |
Max. short circuit current, module array | 18 / 18 A |
DC input voltage range (Udc min - Udc max) | 80 - 1000 V |
Feed-in start voltage (Udc start) | 80 V |
Nominal input voltage (Udc,r) | 710 V |
MPP voltage range (Umpp min - Umpp max) | 200 - 800 V |
Usable MPP voltage range | 80 - 800 V |
Number of DC connections | 2 + 2 |
Max. PV generator power (Pdc max) | 5,5 kWpeak |
OUTPUT DATA
AC nominal output (Pac,r) | 3680 W |
Max. output power (Pac max) | 3680 VA |
AC output current (Iac nom) | 16 A |
Grid connection (Uac,r) | 1~ NPE 220/230 V |
AC voltage range (Umin - Umax) | 180 - 270 V |
Frequency (fr) | 50 / 60 Hz |
Frequency range (fmin - fmax) | 45 - 65 Hz |
Total harmonic distortion | < 5 % |
Power factor (cos φac,r) | 0,85 - 1 ind,/cap, |
GENERAL DATA
Width | 431 mm |
Height | 645 mm |
Depth | 204 mm |
Weight | 21,5 kg |
Degree of protection | IP 65 |
Protection class | 1 |
Overvoltage category (DC / AC) 1) | 2 / 3 |
Night-time consumption | < 1 W |
Inverter design | Transformerless |
Cooling | Regulated air cooling |
Installation | Indoors and outdoors |
Ambient temperature range | -40°C - +55°C |
Permitted humidity | 0 - 100 % |
Max. altitude 2) | 4,000 m |
DC connection technology | 4x DC+ and 4x DC- screw terminals 2.5 - 16 mm² |
AC connection technology | 3-pin AC screw terminals 2.5 - 16 mm² |
Certificates and compliance with standards | DIN V VDE 0126-1-1/A1, IEC 62109-1/-2, IEC 62116, IEC 61727, |
Interference emission class | B |
EFFICIENCY
Max. efficiency (PV - grid) | 98 % |
European efficiency (ηEU) | 96,8 % |
η at 5% Pac,r 3) | 80,8 / 82,5 / 82,5 % |
η at 10% Pac,r 3) | 86,3 / 93,6 / 91,8 % |
η at 20% Pac,r 3) | 91,6 / 96,2 / 95,2 % |
η at 25% Pac,r 3) | 92,7 / 96,9 / 95,8 % |
η at 30% Pac,r 3) | 93,5 / 97,2 / 96,3 % |
η at 50% Pac,r 3) | 95,0 / 97,7 / 97,3 % |
η at 75% Pac,r 3) | 95,6 / 97,8 / 97,8 % |
η at 100% Pac,r 3) | 95,8 / 98,0 / 97,8 % |
MPP adaptation efficiency | > 99,9 % |
PROTECTION DEVICES
DC insulation measurement | Yes |
Overload behaviour | Operating point shift, power limitation |
DC disconnector | Yes |
DC Reverse polarity protection | Yes |
INTERFACES
Ethernet LAN | Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON) |
6 inputs and 4 digital inputs/outputs | Interface to ripple control receiver |
USB (type A socket) 4) | Data logging, inverter update via USB flash drive |
2x RS422 (RJ45 socket) 4) | Fronius Solar Net |
Signalling output 4) | Energy management (floating relay output) |
External input 4) | S0 meter connection / Evaluation of overvoltage protection |
RS485 | Modbus RTU SunSpec or meter connection
|